The numeric selective protection device is used for operation with DC automatic unit, equipped with an independent release. The protection device provides:

  • DC automatic unit disconnection in case of short circuit current during the preset dwell time;

  • DC automatic unit disconnection in case of overload current;

  • full test of protection device and disconnection circuit, faults indication on LED display;

  • monitoring of automatic unit interlock contacts position;

  • indication of protection actuation;

  • recording of value and duration of overcurrents disconnected by the protection device;

  • data transmission to an upper-level device using RS485 interface (MODBUS RTU protocol).


Specifications

Protection operating current

programmable

Response time

0.02 s…preset time

Reset coefficient

³ 0,95

Power

85 – 260 VDC

Power consumption

£ 5 VA

Basic processor

AduC 812

Dimensions

110 x 120 x 145 mm

Weight

1,4 kg max.

Operating temperature range

0…+70°C

Come back

Вверх