This device provides automatic monitoring of variation of a sum of insulation admittance currents in three phases of a current transformer, previously balanced to minimum, in each connection. The device is used as a part of an automatic operation control system in a power installation.


Specifications

Insulation complex conductance measurement range

0,1 – 4%

Suppression third harmonic and higher harmonics

40

No. of monitored 330 kV current transformers

24

Interface

RS232


KIT FOR BASIC INSULATION MONITORING IN 330 KV CURRENT TRANSFORMERS UNDER OPERATING VOLTAGE


Measured variables:

  1. dielectric loss (tg d) of a current transformer insulation in a monitored connection, relative to a current transformer in a reference connection;

  2. complex admittance (sum of basic insulation leakage currents in three phases), using a selective voltmeter.


Kit components:

  • stationary sensors mounted between the measuring terminal and the current transformer case;

  • connection cabinets, mounted on the supports of “B” phases in the connection;

  • portable measuring circuit, including two cable drums with a shielded cable;

  • connection unit and measuring bridge (P5026);

  • selective voltmeter.