The “PDE-9045-B” panel, a new device intended to replace outdated “PEH” devices, provides automatic maintenance of voltage on DC switchboard buses (ARN-2) and recharging of terminal elements in accumulator batteries (ARN-3).
Specifications
DC mains rated voltage |
220 V |
Power supply rated voltage |
220 – 240 V, 50 Hz |
Power consumption from AC mains |
350 VA |
Voltage level setting range (ARN-2) |
190…260 V |
Voltage setting range (ARN-3) |
7…75 V |
Maximum permissible current (ARN-3) |
4 A |
Voltage control accuracy (ARN-3) |
£ 1% |
Dimensions |
1600 x 600 x 500 mm |
Weight |
90 kg |